Update - We have not seen any active issues up to this point, all systems are fully operational. Our team will continue to monitor all services closely.
Aug 16, 2026 - 10:09 CEST
Update - We are continuing to monitor for any further issues.
Aug 16, 2026 - 03:05 CEST
Monitoring - Service Restoration Update - 15 Aug 2026 – 21:11 CEST

Service has been tentatively restored at our Equinix datacentre, and message delivery is now resuming. Our teams continue to monitor the environment closely and are working through the remaining message backlog.
We will provide further updates as stability is confirmed.

We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 21:11 CEST
Update - Service Restoration Update - 15 Aug 2026 – 20:29 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — Completed
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chillers 7, 8, and 9 Restoration — Completed
• Additional chiller vendors en route — Completed
• Restoration of cooling to the affected areas of second floor (Module 215) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 20:30 CEST
Update - Service Restoration Update - 15 Aug 2026 – 20:02 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — Completed
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chillers 7, 8, and 9 Restoration — Completed
• Additional chiller vendors en route — Completed
• Restoration of cooling to the affected areas of second floor (Module 215) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 20:03 CEST
Update - Service Restoration Update - 15 Aug 2026 – 19:35 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — Completed
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chillers 7, 8, and 9 Restoration — Completed
• Additional chiller vendors en route — Completed
• Restoration of cooling to the affected areas of second floor (Module 215) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 19:35 CEST
Update - Service Restoration Update - 15 Aug 2026 – 19:05 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — Completed
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chillers 7, 8, and 9 Restoration — Completed
• Additional chiller vendors en route — Completed
• Restoration of cooling to the affected areas of second floor (Module 215) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 19:06 CEST
Update - Service Restoration Update - 15 Aug 2026 – 18:39 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — Completed
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chillers 7, 8, and 9 Restoration — Completed
• Additional chiller vendors en route — Completed
• Restoration of cooling to the affected areas of second floor (Module 215) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 18:39 CEST
Update - Service Restoration Update - 15 Aug 2026 – 18:06 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress
• Additional chiller vendors en route - Completed

The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 18:09 CEST
Update - Service Restoration Update - 15 Aug 2026 – 17:39 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress
• Additional chiller vendors en route - Completed

The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 17:40 CEST
Update - Service Restoration Update - 15 Aug 2026 – 17:09 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress
• Additional chiller vendors en route - In Progress

The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 17:11 CEST
Update - Service Restoration Update - 15 Aug 2026 - 16:31 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress
• Additional chiller vendors en route - In Progress

The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 16:32 CEST
Update - Service Restoration Update - 15 Aug 2026 - 16:04 CEST
Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses. We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 16:04 CEST
Update - Service Restoration Update - 2026-08-15 15:42 CEST

Mitigation & Planned Actions
• First leak isolation — Completed
• Second leak isolation — Completed and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 15:41 CEST
Update - Service Restoration Update - 2026-08-15 15:17 CEST

Mitigation & Planned Actions
• First leak closure — Isolated
• Second leak closure — Isolated and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 15:17 CEST
Update - Service Restoration Update - 2026-08-15 14:53 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 14:54 CEST
Update - Service Restoration Update - 2026-08-15 14:20 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 14:20 CEST
Update - Service Restoration Update - 2026-08-15 13:53 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — In Progress

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 13:53 CEST
Update - Service Restoration Update - 2026-08-15 13:24 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chilled water refilling — Completed
• Second chilled water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — Completed
• Chiller test run (one chiller at a time) — Planned
Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 13:24 CEST
Update - Service Restoration Update - 2026-08-15 12:57 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chiller water refilling — In Progress
• Second chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Buffer tanks refill — In Progress
• Chiller test run (one chiller at a time) — Planned
Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 12:56 CEST
Update - Service Restoration Update - 2026-08-15 12:26 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chiller water refilling — In Progress
• Second chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — Planned

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 12:25 CEST
Update - Service Restoration Update - 2026-08-15 11:55 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chiller water refilling — In Progress
• Second chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — Planned

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 11:56 CEST
Update - Service Restoration Update - 2026-08-15 11:28 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chiller water refilling — In Progress
• Second chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — Planned

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 11:29 CEST
Update - Service Restoration Update - 2026-08-15 11:02 CEST

Mitigation & Planned Actions
• Leak closure — Completed
• Second leak closure — Isolated and Investigation In Progress
• Chiller water refilling — In Progress
• Second chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Restoration work In Progress
• Fire system vendor to restore fire system — Restoration work In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — Planned

Suspected Initial Cause
The suspected initial cause is a cooling system failure due to a leak in the chilled water system.
We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 11:03 CEST
Update - Service Restoration Update - 2026-08-15 10:30 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Verifying
• Chiller water refilling — In Progress (nearly complete)
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Onsite, Restoration In Progress
• Fire system vendor to restore fire system — Onsite, Restoration In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — In Progress

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 10:31 CEST
Update - Service Restoration Update - 2026-08-15 10:01 CEST

Mitigation & Planned Actions (Mitto DR Activation in progress)
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress (nearly complete)
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress (nearly complete)
• Chiller vendor engagement — Enroute to the site
• Fire system vendor to restore fire system — Arrived on-site, Restoration In Progress
• Elevator restoration — Completed
• Chiller test run (one chiller at a time) — In Progress

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted for approximately three hours, and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 10:02 CEST
Update - Service Restoration Update - 2026-08-15 09:33 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress (nearly complete)
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Enroute to the site (ETA 09:30 Site Local Time)
• Fire system vendor to restore fire system — Enroute to the site (ETA 09:30 Site Local Time)
• Elevator restoration — Completed
• Pump operation to purge air from system — Planned
• Chiller test run (one chiller at a time) — Planned

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted for approximately three hours, and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.
We appreciate your patience and understanding while we work to fully restore the affected services.

Aug 15, 2026 - 09:33 CEST
Update - Service Restoration Update - 2026-08-15 08:58 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Chiller vendor engagement — Enroute to the site (ETA 09:30 Site Local Time)
• Fire system vendor to restore fire system — Enroute to the site (ETA 09:30 Site Local Time)
• Elevator restoration — Completed

Aug 15, 2026 - 09:00 CEST
Update - Service Restoration Update - 2026-08-15 08:31 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — Enroute to the site (ETA 20 minutes)
• Fire system vendor to restore fire system — In Progress
• Elevator unavailable— In Progress

We are invoking our Disaster Recovery (DR) environment due to the ongoing datacentre incident. The primary site has been impacted for approximately three hours, and no confirmed restoration time is currently available. We will continue to provide updates as recovery progresses.

Aug 15, 2026 - 08:32 CEST
Update - Service Restoration Update - 2026-08-15 07:57 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Additional hose installation to accelerate refilling process — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — Enroute to the site (ETA 20 minutes)
• Fire protection vendor activation — Enroute to the site

Aug 15, 2026 - 07:57 CEST
Update - Service Restoration Update - 2026-08-15 07:29 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Additional hose installation to accelerate refilling process — In Progress
• Mobile dehumidifiers deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — In Progress (ETA 20 minutes)
• Fire protection vendor activation — Enroute to the site

Aug 15, 2026 - 07:30 CEST
Update - Service Restoration Update - 2026-08-15 06:58 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Additional hose installation to accelerate refilling process — In Progress
• Mobile dehumidifier deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — In Progress (ETA one hour)

Aug 15, 2026 - 06:58 CEST
Update - Service Restoration Update - 2026-08-15 06:32 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Mobile dehumidifier deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — In Progress (ETA one hour)

Aug 15, 2026 - 06:33 CEST
Identified - Service Restoration Update - 2026-08-15 06:32 CEST

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress
• Mobile dehumidifier deployment — Completed
• Water clearing from affected areas — In Progress
• Vendor engagement — In Progress (ETA one hour)

Aug 15, 2026 - 06:32 CEST
Investigating - Service Impact: *Outage ongoing in Data Center*.
Start: 2026-08-15 05:10 CEST
End: Ongoing

Description:

Cooling system failure due to a leak in the chilled water system.

Service Status

There is customer impact. Temperatures are affected, with the highest now at 50 degrees Celsius. The leak has been closed up and chiller water is refilling. Customers in the affected data halls are advised to review their business continuity plans.

Mitigation & Planned Actions

Mitigation & Planned Actions
• Issue investigation — Completed
• Leak closure — Completed
• Chiller water refilling — In Progress

Suspected Initial Cause

The suspected initial cause is a cooling system failure due to a leak in the cold water system.

Incident Summary

Equinix IBX Site Staff reports that on 07-JUN-2024 at 14:30 Site Local Time, a pipe from the Computer Room Air Handler (CRAH) unit was leaking, affecting all cooling systems in the facility. The leak has since been closed up and chiller water refilling is underway.

Customer impact:

Customers may experience service degradation, intermittent connectivity, or a complete inability to access hosted services and applications. Updates will be provided as soon as further information becomes available.

Thank you for understanding.

Aug 15, 2026 - 06:13 CEST
Update - Please be informed that effective 16 August 2026, Smart Communications (Philippines) will no longer support handset Delivery Receipts (DLRs).
SMS traffic will continue to be delivered normally.

No action is required from customers.
We appreciate your understanding.

Mitto Support Team

Aug 16, 2026 - 06:00 CEST
Monitoring - Scheduled for Aug 16, 2026

Please be informed that effective 16 August 2026, Smart Communications (Philippines) will no longer support handset Delivery Receipts (DLRs).
SMS traffic will continue to be delivered normally.

No action is required from customers.
We appreciate your understanding.

Mitto Support Team

Aug 14, 2026 - 11:45 CEST
Investigating - Please be advised that currently there is a degradation in delivery to Marshall Islands, MINTA (551-01).

You may experience irregular delivery and inconsistent delivery times when sending to the specified network.

Our dedicated team is working with the MNO to resolve the situation at hand; no estimated time of resolution can be provided yet.

Start: 2026-05-15 12:30 CEST
End: Ongoing

Thank you for understanding.

Jul 22, 2026 - 14:07 CEST
Monitoring - To further enhance the security of the Mitto Dashboard, we will introduce an important update.
Starting from June 23rd 2026. All users will be required to set a new password before they can log in to the platform. This change is mandatory and is part of our ongoing efforts to improve account protection and platform security.
What you need to do:
• Access the Mitto Dashboard login page
• Follow the Password Reset Release Guide
• Create a new secure password to continue using the platform:
https://documentation.mitto.ch/solutions/editor/password-reset-release-guide

Jun 04, 2026 - 10:07 CEST
Monitoring - We would like to announce that Mitto has become the exclusive international messaging partner for Kyrgyzstan MEGA (437-05).

Effective June 1, 2026, all international messaging traffic towards this destination will be supported through Mitto's officially authorized route, ensuring optimal quality, reliability, and compliance.

We look forward to supporting your messaging needs through this partnership.

For more information, please reach out to your Mitto representative.

Jun 01, 2026 - 18:31 CEST
HTTP API Operational
HTTP API Operational
SMPP Operational
SMPP smpp1.mitto.ch Operational
SMPP smpp2.mitto.ch Operational
Customer Portal/Dashboard Operational
Local Degradation Operational
2FA API Operational
cpaas.mittoapi.com/2fa Operational
Number Intelligence Platform Operational
Number Intelligence Platform Operational
Operational
Degraded Performance
Partial Outage
Major Outage
Maintenance

Scheduled Maintenance

NUMBER INTELLIGENCE PLATFORM PLANNED MAINTENANCE Aug 17, 2026 06:00-08:00 CEST

MAINTENANCE INFORMATION

Dear Customer,

We would like to inform you about upcoming maintenance on our Number Intelligence platform. As part of this process, we will be implementing a service configuration update aimed at enhancing the stability of our services.

The maintenance is scheduled to take place during the following time window:
Start: 17.08.2026. 04:00 UTC
End: 17.08.2026. 06:00 UTC

While no impact is anticipated during the maintenance window, there is a slight possibility of short outages.

If you have any questions, feel free to reach out to support@mitto.ch.

Thank you for your understanding and cooperation.

Posted on Aug 05, 2026 - 09:20 CEST

Aug 17, 2026

No incidents reported today.

Aug 16, 2026

Unresolved incidents: [ONGOING] MITTO'S INCIDENT NOTIFICATION, NOTIFICATION - Philippines Smart Communications – Handset DLR.

Aug 15, 2026

Unresolved incident: DELIVERY DEGRADATION Marshall Islands, MINTA (551-01).

Aug 14, 2026

Aug 13, 2026

No incidents reported.

Aug 12, 2026

No incidents reported.

Aug 11, 2026

No incidents reported.

Aug 10, 2026

No incidents reported.

Aug 9, 2026

No incidents reported.

Aug 8, 2026

No incidents reported.

Aug 7, 2026

No incidents reported.

Aug 6, 2026

No incidents reported.

Aug 5, 2026

No incidents reported.

Aug 4, 2026

No incidents reported.

Aug 3, 2026

No incidents reported.